Key features

  • Electrodynamometer movement with spring-mounted jewel bearing suspension, 90 degree deflection
  • Knife-edge pointer about 140 mm long with anti-parallax mirror scale
  • Rugged Bakelite case with carrying handle; wooden case version for DPF3
  • Designed for use in the horizontal position
  • Made in India by Goliya Instruments, Mumbai
  • Calibrated at cos phi = 1 (unity power factor)
  • SPW1 with up to 2 current x 3 potential ranges

Specifications

Measurement
MovementElectrodynamometer, 90 degree deflection
Calibrationcos phi = 1 (UPF)
AccuracySPW1 class 1.0 between 10 % and 100 % of scale (0.5 optional); DPW3 class 1.5 (1.0 optional)
StandardsIS 1248, EN 60051
Ranges
SPW1 currentSingle range 0.5, 1, 2.5, 5, 10 A; dual range 0.5/1, 1/2, 2.5/5, 5/10, 10/20, 15/30 A
SPW1 potential150 ... 600 V single; 50/100 ... 300/600 V dual; 62.5/125/250, 75/150/300, 150/300/600, 125/250/500 V triple
DPW3 (3-phase 3-wire, double element)Current 0.5/1, 1/2, 2.5/5, 5/10, 10/20 A; potential 62.5/125, 75/150, 125/250, 250/500, 110/440, 300/600 V
Construction
HeightSPW1 98 mm, DPW3 145 mm; front 180 x 208 mm
Pointer and scaleKnife-edge pointer approx. 140 mm, anti-parallax mirror scale
CaseBakelite housing with ABS bottom base; carrying handle
Electrical
Insulation resistance> 20 Mohm at 500 V DC
Test voltage2 kV for 1 minute at 50 Hz
Environment
Operating conditions-10 ... +55 C, RH < 90 %
Storage-10 ... +70 C, RH < 90 %
General
Optional accessoryCarrying case
Other rangesAvailable on request, subject to technical feasibility