Mean Well TDR-480-24 DIN Rail Power Supply 24 V, 20 A, 480 W, 3-Phase Input
- Brand
- Mean Well
- Model number
- TDR-480-24
- Category
- DIN-Rail Power Supplies
Mean Well TDR-480-24, a DIN rail power supply for 3-phase input from the TDR-480 series for 340-550 V AC input, up to 92.5% efficient, for control panels fed from a 3-phase supply.
Price and availability on request
Key features
- Three-Phase 340 ~ 550VAC wide range input (Dual phase operation possible)
- Width only 85.5mm
- Built-in active PFC function compliance to BS EN/EN61000-3-2
- High efficiency 93% and low power dissipation
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DlN rail TS-35/7.5 or 15
- UL508(industrial control equipment)approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- Optional DC OK relay contact
- 3 years warranty
Specifications
| DC voltage | 24V |
|---|---|
| Rated current | 20A |
| Current range | 0 ~ 20A |
| Rated power | 480W |
| Ripple & noise (max.) | 150mVp-p |
| Voltage adj. range | 24 ~ 28V |
| Voltage tolerance | ±1.0% |
| Line regulation | ±0.5% |
| Load regulation | ±1.0% |
| Setup, rise time | 1200ms, 60ms/400VAC 800ms, 60ms/500VAC at full load |
| Hold up time (typ.) | 20ms / 400VAC 20ms / 500VAC at full load |
| Voltage range | Three-Phase 340 ~ 550VAC (Dual phase operation possible) 480 ~ 780VDC |
|---|---|
| Frequency range | 47 ~ 63Hz |
| Power factor (typ.) | PF≧0.9/400VAC PF≧0.88/500VAC at full load |
| Efficiency (typ.) | 92.5% |
| AC current (typ.) | 0.85A/400VAC 0.7A/500VAC |
| Inrush current (typ.) | COLD START 50A |
| Leakage current | <3.5mA/ 530VAC |
| Overload | 105 ~ 130% rated output power; Protection type : Constant current limiting, unit will shut down after 3 sec. ,re-power on to recover |
|---|---|
| Over voltage | 29 ~ 33V; Protection type : Shut down o/p voltage, re-power on to recover |
| Over temperature | Shut down o/p voltage, recovers automatically after temperature goes down |
| Working temp. | -30 ~ +70℃ (Refer to "Derating Curve") |
|---|---|
| Working humidity | 20 ~ 95% RH non-condensing |
| Storage temp., humidity | -40 ~ +85℃, 10 ~ 95% RH |
| Temp. coefficient | ±0.03%/℃ (0 ~ 50℃) |
| Vibration | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X |
| Safety standards | UL508, IEC62368-1,UL62368-1, AS/NZS 62368.1, BIS IS13252(Part1)(only for 24V),EAC TPTC 004 approved,; Design refer to BS EN/EN62368-1 |
|---|---|
| Withstand voltage | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC |
| Isolation resistance | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH |
| Dimension | 85.5*125.2*128.5mm (W*H*D) |
|---|