Mean Well TDR-240-24 DIN Rail Power Supply 24 V, 10 A, 240 W, 3-Phase Input
- Brand
- Mean Well
- Model number
- TDR-240-24
- Category
- DIN-Rail Power Supplies
Mean Well TDR-240-24, a DIN rail power supply for 3-phase input from the TDR-240 series for 340-550 V AC input, for control panels fed from a 3-phase supply.
Price and availability on request
Key features
- Three-Phase 340 ~ 550VAC wide range input (Dual phase operation possible)
- 63mm slim width
- Built-in passive PFC function compliance to BS EN/EN61000-3-2
- High efficiency 92% and low power dissipation
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Full power between -30~+60°C
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL61010(industrial control equipment)approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- DC OK relay contact
- 3 years warranty
Specifications
| DC voltage | 24V |
|---|---|
| Rated current | 10A |
| Current range | 0 ~ 10A |
| Rated power | 240W |
| Ripple & noise (max.) | 100mVp-p |
| Voltage adj. range | 24 ~ 28V |
| Voltage tolerance | ±1.0% |
| Line regulation | ±0.5% |
| Load regulation | ±1.0% |
| Setup, rise time | 2000ms, 60ms/400VAC 1500ms, 60ms/500VAC at full load |
| Hold up time (typ.) | 20ms / 400VAC 40ms / 500VAC at full load |
| Voltage range | Three-Phase 340 ~ 550VAC (Dual phase operation possible in connecting L1,L3,FG or L2,L3,FG) or 480 ~ 780VDC |
|---|---|
| Frequency range | 47 ~ 63Hz |
| Power factor (typ.) | 92% |
| Efficiency (typ.) | PF≧0.53/400VAC PF≧0.52/500VAC at full load |
| AC current (typ.) | 0.69A/400VAC 0.6A/500VAC |
| Inrush current (typ.) | COLD START 50A |
| Leakage current | <2mA/ 530VAC |
| Overload | Protection type : Constant current limiting, unit will hiccup after 3; 105 ~ 130% rated output power |
|---|---|
| Over voltage | 30 ~ 36V; Protection type : Hiccup mode, recovers automatically after fault condition is removed. |
| Over temperature | Shut down o/p voltage, recovers automatically after temperature goes down |
| DC OK relay contact ratings (max.) | 60VDC/0.3A, 30VDC/1A, 30VAC/0.5Aresistive load |
|---|
| Working temp. | -30 ~ +70℃ (Refer to "Derating Curve") |
|---|---|
| Working humidity | 20 ~ 95% RH non-condensing |
| Storage temp., humidity | -40 ~ +85℃, 10 ~ 95% RH non-condensing |
| Temp. coefficient | ±0.05%/℃ (0 ~ 60℃) |
| Vibration | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X |
| Operating altitude | 5000 meters |
| Over voltage category | Ⅲ;According to EN61558, EN50178, EN60664-1, EN62477-1, EN60204-1; altitude up to 2000 meters |
| Safety standards | UL61010-1, UL61010-2-201, BS EN/EN61558-1, BS EN/EN61558-2-16, BIS IS13252(Part1)(only for 24V), EAC TPTC 004 approved,; design refer toAS/NZS61558-1/-2-16 |
|---|---|
| Withstand voltage | I/P-O/P:4.87KVAC I/P-FG:2.4KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC |
| Isolation resistance | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH |
| Dimension | 63*125.2*113.5mm (W*H*D) |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.