Mean Well RSP-1600-27 Enclosed Switching Power Supply 27 V, 59 A, 1593 W
- Brand
- Mean Well
- Model number
- RSP-1600-27
Mean Well RSP-1600-27, an enclosed switching power supply from the RSP-1600 series for 90-264 V AC input, up to 92% efficient, for machines, control panels and LED systems.
Price and availability on request
Key features
- Universal AC input / Full range
- (Withstand 300VAC surge input for 5 seconds)
- Built-in active PFC function
- High efficiency up to 93%
- Forced air cooling by built-in DC fan
- Output voltage and constant current level programmable
- Active current sharing up to 9600W (5+1)
- Built-in remote ON-OFF control / remote sense /auxiliary power / DC OK signal / OTP alarm signal
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Optional PMBus or CANBus protocol
- 5 years warranty
Specifications
| DC voltage | 27V |
|---|---|
| Rated current | 59A |
| Current range | 0 ~ 59A |
| Rated power | 1593W |
| Ripple & noise (max.) | 200mVp-p |
| Voltage adj. range | 26.5 ~ 33.5V |
| Voltage tolerance | ±1.0% |
| Line regulation | ±0.5% |
| Load regulation | ±0.5% |
| Setup, rise time | 1500ms, 60ms/230VAC at full load |
| Hold up time (typ.) | 16ms / 230VAC at 75% load 10ms / 230VAC at full load |
| Voltage range | 90 ~ 264VAC 250 ~ 370VDC |
|---|---|
| Frequency range | 47 ~ 63Hz |
| Power factor (typ.) | 0.97/230VAC at full load |
| Efficiency (typ.) | 92% |
| AC current (typ.) | 14A/115VAC 8A/230VAC 15A/115VAC 8.5A/230VAC |
| Inrush current (typ.) | COLD START 35A/230VAC |
| Leakage current | <2mA / 230VAC |
| Overload | 105 ~ 115% rated current; Protection type : Constant current limiting, shut down O/P voltage after 5 sec. After O/P voltage falls, re-power on to recover |
|---|---|
| Over voltage | 35.2 ~ 41.9V; Protection type : Shut down o/p voltage, re-power on to recover |
| Over temperature | Protection type : Shut down o/p voltage, recovers automatically after temperature goes down |
| Voltage programmable(PV) | Adjustment of output voltage is allowable to 40 ~ 125% of nominal output voltage (60 ~ 125% for 12V).; Please refer to the Function Manual. |
|---|---|
| Current programmable(PC) | Adjustment of constant current level is allowable to 20 ~ 100% of rated current.; Please refer to the Function Manual. |
| Auxiliary power | 5V @ 0.3A, 12V @ 0.8A |
| Remote ON-OFF control | By electrical signal or dry contact Power ON:short Power OFF:open. Please refer to the Function Manual |
| Remote sense | Compensate voltage drop on the load wiring up to 0.5V. Please refer to the Function Manual |
| Alarm signal | Isolated signal output for T-alarm and DC OK |
| Working temp. | -30 ~ +70℃ (Refer to "Derating Curve") |
|---|---|
| Working humidity | 20 ~ 90% RH non-condensing |
| Storage temp., humidity | -40 ~ +85℃, 10 ~ 95% RH non-condensing |
| Temp. coefficient | ±0.03%/℃ (0 ~ 50℃) |
| Vibration | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
| Safety standards | UL62368-1, CAN/CSA C22.2 No. 62368-1, TUV BS EN/EN62368-1, BSMI CNS15598-1, AS/NZS62368.1, EAC TP TC 004 approved |
|---|---|
| Withstand voltage | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC |
| Isolation resistance | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH |
| Dimension | 300*85*41mm (L*W*H) |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.