Mean Well NDR-480-24 DIN Rail Power Supply 24 V, 20 A, 480 W
- Brand
- Mean Well
- Model number
- NDR-480-24
- Category
- DIN-Rail Power Supplies
Mean Well NDR-480-24, a DIN rail power supply from the NDR-480 series for 90-264 V AC input, up to 92.5% efficient, for control panels.
Price and availability on request
Key features
- Universal AC input / Full range
- Built-in active PFC function
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- 100% full load burn-in test
- 3 years warranty
Specifications
| DC voltage | 24V |
|---|---|
| Rated current | 20A |
| Current range | 0 ~ 20A |
| Rated power | 480W |
| Ripple & noise (max.) | 150mVp-p |
| Voltage adj. range | 24 ~ 28V |
| Voltage tolerance | ±1.0% |
| Line regulation | ±0.5% |
| Load regulation | ±1.0% |
| Setup, rise time | 1500ms, 100ms/230VAC 3000ms, 100ms/115VAC at full load |
| Hold up time (typ.) | 16ms/230VAC 16ms/115VAC at full load |
| Voltage range | 90 ~ 264VAC 127 ~ 370VDC |
|---|---|
| Frequency range | 47 ~ 63Hz |
| Power factor (typ.) | PF>0.98/115VAC, PF>0.94/230VAC at full load |
| Efficiency (typ.) | 92.5% |
| AC current (typ.) | 4.8A/115VAC 2.4A/230VAC |
| Inrush current (typ.) | 20A/115VAC 35A/230VAC |
| Leakage current | <2mA / 240VAC |
| Overload | 105 ~ 130% rated output power; Protection type : Constant current limiting, unit will shut down after 3 sec., re-power on to recover |
|---|---|
| Over voltage | 29 ~ 33V; Protection type : Shut down o/p voltage, re-power on to recover |
| Over temperature | Shut down o/p voltage, recovers automatically after temperature goes down |
| Working temp. | -20 ~ +70℃ (Refer to "Derating Curve") |
|---|---|
| Working humidity | 20 ~ 95% RH non-condensing |
| Storage temp., humidity | -40 ~ +85℃, 10 ~ 95% RH |
| Temp. coefficient | ±0.03%/℃ (0 ~ 50℃) |
| Vibration | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X |
| Safety standards | Ul508, TUV BS EN/EN62368-1, EAC TP TC 004 ,BSMI CNS15598-1 , IS13252(Part1)/IEC60950-1(except for 48V) approved;; (meet BS EN/EN60204-1) |
|---|---|
| Withstand voltage | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
| Isolation resistance | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH |
| EMC emission | Compliance to BS EN/EN55032 (CISPR32),BS EN/EN61204-3 Class B,BS EN/EN61000-3-2,-3,EAC TP TC 020,CNS15936 Class B |
| EMC immunity | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11,BS EN/EN55035,BS EN/EN61000-6-2 (BS EN/EN50082-2),BS EN/EN61204-3,; heavy industry level, EAC TP TC 020 |
| MTBF | 1041.6K hrs min. Telcordia SR-332 (Bellcore) ; 146.8K hrs min. MIL-HDBK-217F (25℃) |
|---|---|
| Dimension | 85.5*125.2*128.5mm (W*H*D) |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.