Mean Well LRS-600N2-48 Enclosed Power Supply 48 V, 12.5 A, 600 W, High Peak
- Brand
- Mean Well
- Model number
- LRS-600N2-48
Mean Well LRS-600N2-48, a high peak power enclosed power supply from the LRS-600N2 series for 90-132 / 180-264 V AC input, up to 92% efficient, for machines, control panels and LED systems.
Price and availability on request
Key features
- AC input range selectable by switch
- Withstand 300VAC surge input for 5 second
- Up to 200% peak power capability
- Protections: Short circuit / Overload / Over voltage /Over temperature
- Forced air cooling
- Built-in cooling Fan ON-OFF control
- Compliance to IEC/BS EN/EN61558-1 and 62368-1
- Withstand 5G vibration test
- Over voltage category Ⅲ(OVC Ⅲ)
- High operating temperature up to 65℃
- Operating altitude up to 2000 meters
- 3 years warranty
Specifications
| DC voltage | 48V |
|---|---|
| Rated current | 12.5A |
| Current range | 0 ~ 12.5A |
| Rated power | 600W |
| Ripple & noise (max.) | 360mVp-p |
| Voltage adj. range | 45.6 ~ 52.8V |
| Voltage tolerance | ±1.0% |
| Line regulation | ±0.5% |
| Load regulation | ±0.5% |
| Setup, rise time | 1300ms, 50ms/230VAC 1300ms,50ms/115VAC at full load |
| Hold up time (typ.) | 20ms/230VAC 16ms/115VAC at full load |
| Voltage range | 90 ~ 132VAC / 180 ~ 264VAC by switch 255 ~ 370VDC (swith on 230VAC) |
|---|---|
| Frequency range | 47 ~ 63Hz |
| Efficiency (typ.) | 92% |
| AC current (typ.) | 12A/115VAC 7.5A/230VAC |
| Inrush current (typ.) | 35A/115VAC 60A/230VAC |
| Leakage current | <2mA / 240VAC |
| Over load | Output power >105% rated for more than 5 seconds then shut down o/p voltage, re-power on to recover; Constant current limiting for outpu t power >200% rated for more than 5 seconds and then shut down o/p voltage,; re-power on to recover |
|---|---|
| Over voltage | 55.2 ~ 64.8V; Protection type : Shut down o/p voltage, re-power on to recover |
| Over temperature | Shut down o/p voltage, re-power on to recover |
| Fan ON/OFF control (typ.) | RTH3≧50℃ FAN ON, ≦40℃ FAN OFF |
|---|
| Working temp. | -20 ~ +65℃ (Refer to "Derating Curve") |
|---|---|
| Working humidity | 20 ~ 90% RH non-condensing |
| Storage temp., humidity | -40 ~ +85℃, 10 ~ 95% RH |
| Temp. coefficient | ±0.03%/℃ (0 ~ 50℃) |
| Vibration | 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes |
| Over voltage category | Ⅲ:According to EN61558,EN50178,EN60664-1,EN62477-1;altitude up to 2000 meters |
| Safety standards | BS IEC/UL 62368-1, EAC TP TC 004, BIS IS13252(Part1):2010/IEC60950-1:2005(except for 48V),; BSMI CNS15598-1,GB 4943.1, BS EN/EN61558-1,BS EN/EN61558-2-16,; design refer to AS/NZS61558.1/2.16,AS/NZS62368.1 |
|---|---|
| Withstand voltage | I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
| Isolation resistance | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC / 25℃/ 70% RH |
| EMC emission | Compliance to EAC TP TC 020, BSMI CNS15936 |
| EMC immunity | Compliance to EAC TP TC 020 |
| MTBF | 1336.2K hrs min. Telcordia SR-332(Bellcore) ; 230.8 K hrs min. MIL-HDBK-217F (25℃) |
|---|---|
| Dimension | 225*124*41mm (L*W*H) |
| Packing | 0.95Kg/12pcs/12.4Kg/0.77CUFT |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.