Mean Well HDR-60-24 DIN Rail Power Supply 24 V, 2.5 A, 60 W

Model number
HDR-60-24

Mean Well HDR-60-24, a DIN rail power supply from the HDR-60 series, up to 90% efficient, for control panels.

Price and availability on request

Request a quote

Sent with the product details: Mean Well HDR-60-24 DIN Rail Power Supply 24 V, 2.5 A, 60 W.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Ultra slim design with 52.5mm(3SU) width
  • Universal input 85~264VAC(277VAC operational)
  • No load power consumption<0.3W lsolation class Ⅱ
  • Pass LPS (Limited power source)
  • DC output voltage adjustable
  • Protections : Short circuit / Overload / Over voltage
  • Cooling by free air convection (working temperature:-30~+70°C)
  • DIN rail TS-35/7.5 or 15 mountable
  • LED indicator for power on
  • 3 years warranty

Specifications

Output
DC voltage24V
Rated current2.5A
Current range0 ~ 2.5A
Rated power60W
Ripple & noise (max.)150mVp-p
Voltage adj. range21.6 ~ 29V
Voltage tolerance±1.0%
Line regulation±1.0%
Load regulation±1.0%
Hold up time (typ.)30ms/230VAC 12ms/115VAC at full load
Input
Voltage range85 ~ 264 VAC (277VAC operational ) 120 ~ 370 VDC (390VDC operational )
Frequency range47 ~ 63Hz
Efficiency (typ.)90%
AC current (typ.)1.2A/115VAC 0.8A/230VAC
Inrush current (typ.)COLD START 30A/115VAC 60A/230VAC
Protection
Overload105 ~ 160% rated output power; Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed; Constant current limiting;%
Over voltage30 ~ 36V; Protection type : Shut down o/p voltage, re-power on to recover
Environment
Working temp.-30 ~ +70℃ (Refer to "Derating Curve")
Working humidity20 ~ 90% RH non-condensing
Storage temp., humidity-40 ~ +85℃, 10 ~ 95% RH non-condensing
Temp. coefficient±0.03%/℃ (0 ~ 50℃) RH non-condensing
Vibration10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
Operating altitude2000 meters
Over voltage categoryⅢ;According to EN61558, EN50178,EN60664-1, EN62477-1;altitude up to 2000 meters
Safety & EMC
Safety standardsUL62368-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, IEC62368-1, EAC TP TC 004, BSMI CNS15598-1,; BIS IS13252(Part1): 2010/IEC 60950-1:2005(NOTE 6) approved; Design refer to BS EN/EN62368-1
Withstand voltageI/P-O/P:4 KVAC
Others
MTBF3524.8K hrs min. Telcordia SR-332 (Bellcore) ; 927.6K hrs min. MIL-HDBK-217F (25℃)
Dimension52.5*90*54.5mm (W*H*D)
Packing190g;60pcs/13Kg/0.91CUFT

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.