Mean Well DDR-240B-24 DC-DC Converter 16.8-33.6 V DC In, 24 V, 10 A, 240 W, DIN Rail

Model number
DDR-240B-24

Mean Well DDR-240B-24 DC-DC converter from the DDR-240 series, taking 16.8-33.6 V DC input and giving a regulated 24 V output at up to 90% efficiency. Snaps onto a DIN rail.

Price and availability on request

Request a quote

Sent with the product details: Mean Well DDR-240B-24 DC-DC Converter 16.8-33.6 V DC In, 24 V, 10 A, 240 W, DIN Rail.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Specifications

Output
DC voltage24V
Rated current10A
Current range0 ~ 10A
Rated power240W
Ripple & noise (max.)80mVp-p
Voltage adj. range24 ~ 28V
Voltage tolerance±1.0%
Line regulation±0.5%
Load regulation±1.0%
Setup, rise time500ms, 60ms
Input
Continuous voltage range16.8 ~ 33.6Vdc; 14.4 ~ 16.8Vdc
Efficiency (typ.)90%
DC current (typ.)11.2A @24Vdc
Inrush current (typ.)30A
Interruption of voltage supplyEN50155:2007-B/C- type comply with S2 level (10ms)@ 70% load ; D-type comply with S2 level (10ms)@ full load; EN50155:2017-Comply with S1 level
Protection
OverloadNormally works within 150% rated output power for more than 3 seconds and then constant current protection 105~135%; rated output power with auto-recovery
Over voltage28.8 ~ 35V; Protection type : Shut down o/p voltage, re-power on to recover
Over temperatureShut down o/p voltage, re-power on to recover
Under voltage lockout24Vin (B - type) :Power ON≥16.8V ,; OFF≤16.5V
Function
DC OK relay contact ratings (max.)30Vdc/1A resistive load
Current sharingUp to 960W (3+1 units). Please refer to the Function Manual
Remote ON-OFF controlPlease refer to the Function Manual
Environment
Working temp.-40 ~ +70℃ (Refer to "Derating Curve")
Working humidity5 ~ 95% RH non-condensing
Storage temp., humidity-40 ~ +85, 5 ~ 95% RH non-condensing
Temp. coefficient±0.03%/℃ (0 ~ 55℃)
VibrationComponent:10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373
Operating altitude5000 meters
Safety & EMC
Safety standardsIEC 62368-1, UL 62368-1, EAC TP TC 004, AS/NZS 62368.1 approved
Withstand voltageI/P-O/P:4KVdc I/P-FG:2.5KVdc O/P-FG:0.71KVdc
Railway standardCompliance to BS EN/EN45545-2 for fire protection ; Meet BS EN/EN50155 / IEC60571 including IEC61373 for shock & vibration,; BS EN/EN50121-3-2 for EMC
Others
MTBF1415.6K hrs min. Telcordia SR-332 (Bellcore) ; 189.9K hrs min. MIL-HDBK-217F (25℃)
Dimension40*125.2*113.5mm (W*H*D)
Other specifications
Current peak power15A; 360W (3sec.)

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.