HTC Instruments CE-8202 Earth Clamp Tester with Leakage Current

Model number
CE-8202

Clamp-on earth resistance tester, 0 – 1200 Ω, with leakage current 0.00 mA – 20 A: measures earth resistance without disconnecting the earth rod or driving test spikes. 9,999 counts, 300-group memory.

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: HTC Instruments CE-8202 Earth Clamp Tester with Leakage Current.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Earth resistance by clamping, without auxiliary spikes
  • Resistance range 0 – 1200 Ω
  • Leakage current 0.00 mA – 20 A
  • Identifies interference signals ("NOISE" symbol when interference current is large)
  • 4 digits, 9,999 counts
  • Jaw size 55 × 32 mm
  • Data logging, 300 groups, with review
  • Alarm
  • Data hold
  • Auto power off
  • For multi-point, limited-point and single-point grounding systems
  • 1 Ω and 10 Ω test rings for checking accuracy
  • Double insulation
  • Shock-proof, dust-proof and moisture-proof

Specifications

Earth resistance (clamp method)
Range0 – 1200 Ω
Ranges (resolution)0.010 Ω – 0.099 Ω (0.001 Ω), 0.10 Ω – 0.99 Ω (0.01 Ω), 1.0 Ω – 49.9 Ω (0.1 Ω), 50.0 Ω – 99.5 Ω (0.5 Ω), 100 Ω – 199 Ω (1 Ω), 200 Ω – 395 Ω (5 Ω), 400 Ω – 590 Ω (10 Ω), 600 Ω – 880 Ω (20 Ω), 900 Ω – 1200 Ω (30 Ω)
Accuracy0.010 Ω – 0.099 Ω: ±⁠(1% + 0.01 Ω); 0.10 Ω – 0.99 Ω: ±⁠(1% + 0.01 Ω); 50.0 Ω – 99.5 Ω: ±⁠(1.5% + 0.5 Ω); 100 Ω – 199 Ω: ±⁠(2% + 1 Ω); 200 Ω – 395 Ω: ±⁠(5% + 5 Ω); 400 Ω – 590 Ω: ±⁠(10% + 10 Ω); 600 Ω – 880 Ω: ±⁠(20% + 20 Ω); 900 Ω – 1200 Ω: ±⁠(25% + 30 Ω)
Leakage current
Ranges (resolution)0.00 mA – 9.95 mA (0.01 mA), 10.0 mA – 99.0 mA (0.1 mA), 100 mA – 300 mA (1 mA), 0.30 A – 2.99 A (0.01 A), 3.0 A – 9.9 A (0.1 A), 10.0 A – 20.0 A (0.1 A)
Accuracy0.00 – 9.95 mA: ±⁠(2.5% + 1 mA); 10.0 – 99.0 mA: ±⁠(2.5% + 5 mA); 100 – 300 mA: ±⁠(2.5% + 10 mA); 0.30 – 2.99 A: ±⁠(2.5% + 0.1 A); 3.0 – 9.9 A: ±⁠(2.5% + 0.3 A); 10.0 – 20.0 A: ±⁠(2.5% + 0.5 A)
General
Display4 digits, 9,999 counts, LCD
Jaw size55 × 32 mm
Measuring rate2 per second
Memory300 groups, with review
Measuring methodMutual inductance
PowerDC 6 V (4 × 1.5 V AA dry batteries)
DimensionsH 285 × W 85 × D 58 mm
WeightApprox. 1180 g including battery
AccessoriesCheck ring, manual, warranty card, battery and hard carry case