| Measurement lines | 1-phase-2-wire, 1-phase-3-wire, 3-phase-3-wire, 3-phase-4-wire |
|---|
| No. of PW8001 input units | Max. 8 units (mix and match) |
|---|
| Type of input unit | U7001 2.5 MS/s INPUT UNIT U7005 15 MS/s INPUT UNIT |
|---|
| Measurement frequency band | U7001: DC, 0.1 Hz to 1 MHz U7005: DC, 0.1 Hz to 5 MHz |
|---|
| Sampling | U7001: 2.5 MHz, 16-bit U7005: 15 MHz, 18-bit |
|---|
| Data update rate | 1 ms, 10 ms, 50 ms, 200 ms |
|---|
| Accuracy for power (U7001) | 50/60 Hz: 0.02% of reading + 0.05% of range DC: 0.02% of reading + 0.05% of range 50 kHz : 0.4% of reading + 0.1% of range |
|---|
| Accuracy for power (U7005) | 50/60 Hz : 0.01% of reading + 0.02% of range DC : 0.02% + 0.03% of reading of range 50 kHz: 0.15% of reading + 0.05% of range |
|---|
| Measurement range | Voltage: 6 V, 15 V, 30 V, 60 V, 150 V, 300 V, 600 V, 1500 V Current: (Probe1) 40 mA to 2 kA, (Probe2) 100 mA to 50 kA (Probe1 : Hioki's high-accuracy current sensor interface supports automatic identification and phase shift correction. Probe 2: BNC I/F only for U7001) |
|---|
| Measurement parameters | voltage (U), current (I), active power (P), apparent power (S), reactive power(Q), power factor (λ), phase angle (φ), voltage frequency (fU) , current frequency (fI) , efficiency (η), loss (Loss), voltage ripple factor (Urf), current ripple factor (Irf), current integration (Ih), power integration (WP), voltage peak (Upk), current peak (Ipk) - Harmonics measurement : (Wideband mode: Maximum analysis order 500th, IEC measurement mode) - Waveform recording: recording capacity 5M words × ( [voltage |
|---|
| IEC measurement mode | When the measurement line has a frequency of 50 Hz or 60 Hz, the instrument can perform harmonic measurements according to IEC61000-4-7 and voltage fluctuation/flicker measurements according to IEC61000-4-15 |
|---|
| IEC-compliant harmonic measurement | Compliant with IEC 61000-4-7:2002 Analysis order: Harmonics: 0th to 200th orders, Inter-harmonic: 0.5th to 200.5th orders |
|---|
| IEC-compliant flicker measurement | Compliant with IEC 61000-4-15:2010 Ed 2.0 Flickermeter Class F2 Measurement items: Short-term flicker (Pst), Maximum short-term flicker value (PstMax), Long-term flicker value (Plt), Maximum instantaneous flicker value (PinstMax), Minimum instantaneous flicker value (PinstMin), Relative steady-state voltage change (dc), Maximum relative voltage change (dmax), Period while the relative voltage change exceeds the threshold (Tmax) |
|---|
| Calculation function | Efficiency and loss calculations, User-defined calculations, Delta conversion, Current sensor automatic phase shift calculation |
|---|
| Synchronization measurement | Optical link: Up to two units, 16 channels maximum BNC Synchronization: Up to four units, 32 channels maximum |
|---|
| External interface | USB flash drive, LAN, GP-IB, RS-232C, external control, optical link, BNC sync., CAN or CAN FD |
|---|
| Power supply | 100 V to 240 V AC, 50/60 Hz, 230 VA |
|---|
| Dimensions and mass | Approx. 430 mm (16.93 in) W × 221 mm (8.70 in) H × 361mm (14.21 in) D, Approx. 14kg (493.84 oz) |