Hioki CM4003 AC Leakage Clamp Meter with Output

Brand
Hioki
Model number
CM4003

True RMS AC leakage clamp meter with output and external power supply functions, a sensor for very small leakage currents, 6 mA to 200 A ranges and IEC/EN 61557-13 compliance. Z3210 wireless adapter sold separately.

Price and availability on request

Request a quote

Sent with the product details: Hioki CM4003 AC Leakage Clamp Meter with Output.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Easily transfer measurement data to your smartphone or tablet by using our free app GENNECT Cross or to an Excel® file. (Wireless Adapter Z3210 is necessary)
  • Detect minuscule leakage currents with a newly designed sensor. (Core jaw diameter up to φ 40 mm)
  • Broad measurement range extending from leakage currents to load currents
  • Complies with the performance standard set forth in IEC/EN 61557-13, an international standard on leak clamp meters
  • Solve GFCI and RCD problems quickly
  • Speed up pass/fail judgments with the built-in comparator function
  • Output function (waveform/RMS): use with a recorder to record waveforms and fluctuations
  • External power supply: use an optional AC adapter for continuous, long-term measurement
  • CAT III 300 V

Specifications

Specifications
AC Current range6.000 mA, 60.00 mA, 600.0 mA, 6.000 A, 60.00 A, 200.0 A, 6 ranges, True RMS Basic accuracy 45 Hz - 400 Hz: ±1.0% rdg ±5 dgt (6.000 mA to 6.000 A), ±1.5% rdg ±5 dgt (60.00 A, 200.0 A) Basic accuracy 15 Hz - 45 Hz, 400 Hz - 2 kHz: ±2.0% rdg ±5 dgt Defined accuracy range: 0.060 mA to 200.0 A
AC Voltage rangeN/A
Frequency range15.0 Hz to 2000 Hz
Crest factor3 (other than 200.0 A range), 1.5 (200.0 A range)
Filter functionCut off frequency: 180 Hz ±30 Hz at filter ON (-3 dB)
Output functionRMS (RMS value output), WAVE (waveform output)
Harmonic levels[With Z3210 installed] Current harmonic levels up to 30th, Content factor, Total harmonic distortion ratio *Harmonics can be displayed with our free app GENNECT Cross.
Other functionsMax/ Min/ AVG/ PEAK MAX/ PEAK MIN value display, Display value hold and auto hold; Backlight, Auto power save, Buzzer sound, Event count display, Comparator, Simple event recording, Rush current measurement
DisplayDisplay refresh rate: 5 times/s
Power supply- AA-size alkaline battery (LR6) × 2; Continuous operating time: 48 hr. (without Z3210 installed), 30 hr. (with Z3210 installed and using wireless communications) - AC Adapter Z1013 (5 V DC, 2.6 A)
Core jaw diameterφ 40 mm (1.57 in.)
Dimensions and mass64 mm (2.52 in) W × 233 mm (9.17 in) H × 37 mm (1.46 in) D, 400 g (14.1 oz.)
Supplied with
ContentsConnection Cable L9097 × 1, USB Cable × 1, Carrying case C0203 × 1, Instruction manual × 1, Operating Precautions × 1, AA-size alkaline battery (LR6) × 2
Ordering
Order codeCM4003 (Wireless Adapter Z3210 not included)

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.