Fluke 902 FC True-rms HVAC Clamp Meter
- Brand
- Fluke
- Model number
- 902 FC
- Category
- AC Clamp Meters
True-rms HVAC clamp meter with Fluke Connect: 200 µA DC for flame sensors, resistance to 60 kΩ, capacitance, temperature.
Price and availability on request
Key features
- A wireless Fluke Connect-enabled clamp meter designed specifically for the needs of HVAC technicians
- Offers 200 µA DC current measurements to measure flame rod
- Extends resistance range to measure thermistors up to 60kΩ
- Captures flue gas temperature
- Measures start and run motor capacitors
- Measures variable frequency drive performance
Specifications
| A ac (via Jaw), Resolution | 0.1 A |
|---|---|
| A ac (via Jaw), Accuracy | 2.0% ±5 digit (45-65 Hz); 2.5% ±5 digit (65-400 Hz) |
| A ac (via Jaw), Range | 600.0 A |
| A ac (via Jaw), Crest Factor (50Hz or 60Hz) | 2.5 MIN@220 A; > 1.4 MIN@600 A; Add 2% for CF>400 A |
| V ac | Crest Factor (50Hz or 60Hz) |
| V ac, Resolution | 0.1 V |
| V ac, Accuracy | 1.5% ±5 digits |
| V ac, Range | 600.0 V |
| V dc, Resolution | 0.1 V |
|---|---|
| V dc, Accuracy | 1.5% ±5 digits |
| V dc, Range | 600.0 V |
| Ohms, Resolution | 0.1/1/10 |
|---|---|
| Ohms, Accuracy | 1% ±5 digits |
| Ohms, Range | 600/6000/60.00 kΩ |
| Capacitance, Resolution | 0.1/1 µF |
|---|---|
| Capacitance, Accuracy | 1% ±4 digits |
| Capacitance, Range | 100.0/1000 µF |
| µA, Resolution | 0.1 µA |
|---|---|
| µA, Accuracy | 1% ±5 digits |
| µA, Range | 200 µA |
| Contact temperature, Resolution | 0.1 C/F |
|---|---|
| Contact temperature, Accuracy | 1% ±8 digits |
| Contact temperature, Range | -40 to 400 °C (-40 °F to 752 °F) |
| Continuity beeper, Beeper volume | 75 dBA nom. 15 cm. from case front |
|---|---|
| Continuity beeper, On threshold | <=30 Ω |
| Maximum voltage between any terminal and earth ground | 600 V |
|---|---|
| Battery type | 2 AA alkaline batteries, NEDA 15A, IEC LR6 |
| Temperature | Operating: -10 °C to +50 °C (14 °F to +122 °F); Storage: -40 °C to +60 °C (-40 °F to +140 °F) |
| Operating humidity | Non condensing (< 10 °C [50 °F]), ≤90 % RH (at 10 °C to 30 °C [50 °F to 86 °F]), ≤75 % RH (at 30 °C to 40 °C (86 °F to 104 °F)), ≤45 % RH (at 40 °C to 50 °C (104 °F to 122 °F)) |
| Altitude | Operating: 3,000 m (9,842 ft); Storage: 12,000 m (39,370 ft) |
| Dimensions | 230 x 83.7 x 45.4mm (9.06 x 3.30 x 1.39 in) |
| Weight (meter only) | 419 g (15 oz) |
| Safety | IEC 61010-1, Pollution Degree 2; IEC 61010-2-032: CAT III 600 V; CAT IV 300 V; IEC 61010-2-033: CAT III 600 V; CAT IV 300 V |
| IP Rating | IEC 60529: IP30, non-operating |
| Temperature coefficients | Add 0.1 × specified accuracy for each degree C above 28 °C or below 18 °C |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.
About the 902 FC
The Fluke 902 FC is designed around HVAC service. It measures microamps for flame and pilot sensors, resistance up to 60 kΩ for thermistors, motor start and run capacitors and temperature, and sends readings to the Fluke Connect app. Rated CAT III 600 V / CAT IV 300 V.