Fluke 1630-2 FC Earth Ground Clamp

Brand
Fluke
Model number
1630-2 FC

Stakeless earth ground loop clamp with AC leakage current measurement, for indoor or paved sites; Fluke Connect.

Price and availability on request

Request a quote

Sent with the product details: Fluke 1630-2 FC Earth Ground Clamp.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Test the grounding components of equipment in hard-to-reach spaces, including areas that are indoors or fully paved and do not permit driving auxiliary test stakes
  • AC Leakage Current Measurement: Identify AC leakage without disconnecting your earth ground stake from the grounding system
  • Rugged: Heavy-duty clamp jaw stays in alignment and calibration on tough jobsites
  • Logging measurement: Saves up to 32,760 measurements in memory

Specifications

Electrical Specifications
Maximum voltage to earth ground1000 V
Battery typeAA alkaline IEC/EN LR6 (x4)
Battery lifeMore than 15 hours*
Frequency range40 Hz to 1 kHz
Ingress protectionIEC/EN 60529: IP30 with jaw closed
LCD, Digital reading9999 counts
LCD, Refresh rate4 per second
Operating temperature-10 °C to + 50 °C
Storage temperature-20 °C to + 60 °C
Operating humidityNon condensing (<10 °C) (< 50 °F); ≤90% RH (at 10 °C to 30 °C [50 °F to 86 °F]); ≤75% RH (at 30 °C to 40 °C [86 °F to 104 °F]); ≤45% RH (at 40 °C to 50 °C [104 °F to 122 °F]); (Non condensing)
Operating altitude2000 m (6561 feet)
Storage altitude12 000 m (39,370 feet)
Reference temperature23 °C ±5 °C (73 °F ±9 °F)
Temperature coefficient0.15% x (specified accuracy)/ °C (<18 °C or >28 °C [<64.4 °F or >82.4 °F])
Overload indicationOL
Data logging capacityMinimum of 32,760 measurements
Data logging interval1 second to 59 minutes and 59 seconds
Display reading specification with standard loop resistance
0.474Minimum 0.417; Maximum 0.531
0.5Minimum 0.443; Maximum 0.558
10Minimum 9.55; Maximum 10.45
100Minimum 96; Maximum 104
Safety
GeneralIEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1
MeasurementIEC/EN 61010-2-032: CAT IV 600 V; CAT III 1000 V
Current clamp for leakage current measurementsIEC/EN 61557-13: Class 2, ≤30 A/m
Resistance to earthIEC/EN 61557-5
Effectiveness of thepProtective measuresIEC/EN 61557-16
General Specifications
Conductor size40 mm (1.57 in) approximately
Dimensions (L x W x H)283 x 105 x 48 mm (11.1 x 4.1 x 1.9 in)
Weight880g (31 oz)
WarrantyOne year
Earth Ground Loop Resistance
RangeAccuracy1 ± (% of reading + Ω)
0.025 Ω to 0.249 Ω1.5% + 0.02 Ω
0.250 Ω to 0.999 Ω1.5% + 0.05 Ω
1.000 Ω to 9.999 Ω1.5% + 0.10 Ω
10.00 Ω to 49.99 Ω1.5% + 0.30 Ω
50.00 Ω to 99.99 Ω1.5% + 0.50 Ω
100.0 Ω to 199.9 Ω3.0% + 1.0 Ω
200.0 Ω to 399.9 Ω5.0% + 5.0 Ω
400 Ω to 599 Ω10.0% + 10 Ω
600 Ω to 1500 Ω20.00%
Earth ground leakage current mA
Range, ResolutionAccuracy1 ± (% of reading + mA)
0.200 mA to 3.999 mA1 μA; 2.0% + 0.05 mA
4.00 mA to 39.99 mA10 μA; 2.0% + 0.03 mA
40.0 mA to 399.9 mA100 μA; 2.0% + 0.3 mA
0.400 A to 3.999 A1 mA; 2.0% + 3 mA
4.00 A to 39.99 A10 mA; 2.0% + 30 mA
Supplied with
Contents1630-2 FC Earth Ground Clamp; Hard case; Loop resistance standard; 4 AA batteries; Quick reference guide

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.

About the 1630-2 FC

The Fluke 1630-2 FC measures earth ground loop resistance on multi-grounded systems with just the clamp, so no auxiliary stakes are needed, even indoors or on paved areas. It also measures AC leakage current without disconnecting the earth ground system.