| Pressure Type | Pneumatic type model: Gauge pressure Fluid type model: Gauge pressure or sealed gauge pressure |
|---|
| Pressure | Static |
|---|
| Min display unit | 1 kPa |
|---|
| Rated pressure range | 0 to 1,000 kPa |
|---|
| Display & setting pressure range | -101.3 to 1,100 kPa |
|---|
| Display type | 7 Segment LED, 4 ½ digit |
|---|
| Display accuracy | -10 to 0 ℃: ≤ ±1% F.S., 0 to 50 ℃: ≤ ±0.5% F.S. |
|---|
| Max. pressure | • Pneumatic type: Rated pressure ×1.5 • Fluid type: Rated pressure ×2 |
|---|
| Applicable medium | Fluid type (non-corrosive gas and fluid that do not corrode stainless steel 316L) |
|---|
| Connection type | Cable type / connector type |
|---|
| Cable | Connector type: Ø 4 mm, 5-core, 2 m Cable type: Ø 4 mm, 5-core, 3 m |
|---|
| Wire spec. | AWG24 (0.08 mm, 40-core), insulator diameter: Ø 1 mm |
|---|
| Material | Front case: PC Back case: PA6 Pressure port: SUS304/SUS316L |
|---|
| Protection structure | Connector type: IP40 (IEC standard) Cable type: IP65 (IEC standard) |
|---|
| Unit weight (packaged) | Connector type: ≈ 88 g (≈ 173 g) Cable type: ≈ 90 g (≈ 167 g) |
|---|
| Power supply | 12 - 24 VDC (ripple P-P: ≤ 10%) |
|---|
| Allowable voltage range | 90 to 110% of rated voltage |
|---|
| Current consumption | ≤ 50 mA |
|---|
| Control output | NPN open collector output / PNP open collector output model |
|---|
| Load voltage | ≤ 30 VDC |
|---|
| Load current | ≤ 100 mA |
|---|
| Residual voltage | NPN: ≤ 1 VDC , PNP: ≤ 2 VDC |
|---|
| Hysteresis | According to output operation mode |
|---|
| Repeat error | ±0.2% F.S. ±min display interval |
|---|
| Response time | 2.5, 5, 100, 500, 1000 ms ; 70 ms |
|---|
| Protection circuit | Output short over-current protection circuit |
|---|
| Insulation resistance | ≥ 50 MΩ (500 VDC megger) |
|---|
| Dielectric strength | Between the charging part and the case: 1,000 VAC 50 / 60 Hz for 1 min |
|---|
| Vibration | 1.5 mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 2 hours |
|---|
| Ambient temperature | -10 to 50 ℃, Storage: -20 to 60 ℃ (no freezing or condensation) |
|---|
| Ambient humidity | 30 to 80%RH, Storage: 30 to 80%RH (no freezing or condensation) |
|---|
| Analog output | Current (DC 4 - 20mA ±2% F.S) |
|---|
| Linearity | ≤ ±1% F.S |
|---|
| Zero-point | ≤ DC 4 mA ±2% F.S. |
|---|
| Span | ≤ DC 16 mA ±2% F.S. |
|---|
| Resolution | 1/1000 or 1/2000 (different by pressure type and display unit) |