Autonics MX4W-A-F2 LCD Multi Panel Meter MX4W-A-F2

Model number
MX4W-A-F2
Category
Panel Meters

Autonics MX4W-A-F2 LCD multi panel meter (MX4W Series): DC / AC current input, 1 / 20,000 resolution, 24 - 240 VDC , 24 - 240 VAC 50 / 60 Hz supply, ≤ 100 mA. Order code note: 24-240VDC/VAC(ENG).

Price and availability on request

Request a quote

Sent with the product details: Autonics MX4W-A-F2 LCD Multi Panel Meter MX4W-A-F2.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • LCD display with easy-to-read white PV characters
  • Isolated input and power modules allow powering of multiple units using a single power supply
  • Compact, space-saving design (rear-length: 20 mm): reduced rear-length size by 80 % compared to same DIN size panel meters (MT4W)
  • Various input options (by model); Input options: DC / AC voltage, DC / AC current
  • Maximum allowed input: 500 VDC , 500 VAC , DC 5 A, AC 5 A
  • Display range: -9999 to 9999
  • High / low-limit display scale function
  • AC frequency measurement (range: 0.100 to 1200 Hz)
  • Preset output: OUT1, OUT2 (NPN / PNP open collector output)
  • Power factor display / output function: displays analog outputs (1 - 5 V, 4 - 20 mA) from power factor converters as -0.50 to 1.00 to 0.50
  • Various functions: peak display value monitoring, display cycle delay, zero-point adjustment, peak display value correction, etc.
  • Power supply: 24 - 240 VAC 50 / 60 Hz, 24 - 240 VDC universal

Specifications

Model
SeriesMX4W Series
Order code description24-240VDC/VAC(ENG)
Catalogue model groupMX4W-A-F□
Specifications
Input typeDC / AC current
Max. allowable inputDependent on the input type
+DC input≈ -10 to 110 % F.S. for each measured input range; -DC input: ≈ -110 to 110 % F.S. for each measured input range
AC input≈ 110 % F.S. for each measured input range
Display method12-segment LCD - measurement value display part: white, character height: 19 mm - other display parts: red, green, yellow (indicator: white)
Display accuracyDependent on the ambient temperature; 23 ± 5 ℃ (DC input): ± 0.1 % F.S. rdg ± 2-digit; 23 ± 5 ℃ (AC input): ± 0.3 % F.S. rdg ± 3-digit; 0 to 50 ℃: ± 0.5 % F.S. rdg ± 3-digit
Display cycle0.2 to 5.0 sec (select per 0.1 sec)
Display scale-9999 to 9999 (4-digit)
A / D conversion methodΣΔ (Sigma Delta) analog-to-digital converter
Sampling cycle (DC input)50 ms
Sampling cycle (AC input)16.6 ms
Resolution1 / 20,000
Preset outputNPN / PNP open collector output model
Load voltage≤ 30 VDC
Load current≤ 100 mA
Residual voltageNPN open collector output: ≤ 1 VDC / PNP open collector output: ≤ 2 VDC
Unit weight (packaged)≈ 77 g (≈ 100 g)
Power supply24 - 240 VDC , 24 - 240 VAC 50 / 60 Hz
Permissible voltage range90 to 110 % of rated voltage
Power consumptionDC: ≤ 3 W, AC: ≤ 5 VA
Insulation resistance≥ 100 MΩ (500 VDC megger)
Dielectric strengthBetween the charging part and the case: 3,000 VAC 50 / 60 Hz for 1 min
Noise immunity± 2 kV square wave noise (pulse width: 1 ㎲) by the noise simulator
Vibration0.75 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 2 hours
Vibration (malfunction)0.5 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 10 min
Shock300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction)100 m/s2 (≈ 10 G) in each X, Y, Z direction for 3 times
Ambient temperature-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
Insulation typeSymbol: , double or reinforced insulation (dielectric strength between the measurement input part and the power part: 1 kV)

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.