| Input type | AC current |
|---|
| Max. allowable input | Dependent on the input type |
|---|
| DC input | -5 to 110 % F.S. for each measured input range |
|---|
| AC input | 10 to 110 % F.S. for each measured input range |
|---|
| Display method | 7-segment (red) LED (character height: 14.2 mm) |
|---|
| Display accuracy | Dependent on the ambient temperature; 23 ± 5 ℃: ± 0.3 % F.S. rdg ± 3 digit; -10 to 50 ℃: ± 0.5 % F.S. rdg ± 3 digit |
|---|
| Max. display range | -1999 to 9999 (4 digit) |
|---|
| A / D conversion method | ΣΔ (Sigma Delta) ADC |
|---|
| Sampling cycle | 16.6 ms |
|---|
| Unit weight (packaged) | ≈ 211 g (≈ 326 g) |
|---|
| Preset output | None (indicator) / Relay / NPN open collector / PNP open collector output model |
|---|
| Relay | Contact capacity: 250 VAC 3 A, 30 VDC 3 A Contact composition: N.O ( 1a) |
|---|
| NPN / PNP open collector | Output capacity: ≤ 12 - 24 VDC ± 2 VDC , 50 mA resistive load |
|---|
| Sub output | None (indicator) / BCD Dynamic / Transmission (DC 4 - 20 mA) / Low speed serial / RS485 Communication output model |
|---|
| BCD Dynamic / Low speed serial | NPN open collector output Output capacity: ≤ 12 - 24 VDC , 50 mA resistive load |
|---|
| Transmission (DC 4 - 20 mA) | Resolution: 1/12,000 (load resistance: ≤ 600 Ω) Response time: ≤ 550 ms Output accuracy (23 ± 5 ℃): ± 0.3 % F.S. |
|---|
| RS485 communication | Protocol: Modbus RTU |
|---|
| Power supply | 12 - 24 VDC |
|---|
| Permissible voltage range | 90 to 110 % of rated voltage |
|---|
| Power consumption | 3 W |
|---|
| Insulation resistance | Between external terminal and case: ≥ 100 MΩ (500 VDC megger) |
|---|
| Dielectric strength | Between the charging part and the case : 2,000 VAC 50 / 60 Hz for 1 min |
|---|
| Noise immunity | ± 500 V square wave noise (pulse width: 1 ㎲) by the noise simulator |
|---|
| Vibration | 0.75 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 2 hours |
|---|
| Vibration (malfunction) | 0.5 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 10 min |
|---|
| Shock | 300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times |
|---|
| Shock (malfunction) | 100 m/s2 (≈ 10 G) in each X, Y, Z direction for 3 times |
|---|
| Relay life cycle | Mechanical: ≥ 20,000,000 operations Electrical: ≥ 100,000 operations (250 VAC 3A resistive load) |
|---|
| Ambient temp. | -10 to 50 ℃, storage: -20 to 60 ℃ (freezing or condensation) |
|---|
| Ambient humi. | 35 to 85 %RH, storage: 35 to 85 %RH (freezing or condensation) |
|---|
| Insulation type | Symbol: , double or reinforced insulation (dielectric strength between the measurement input part and the power part: 1 kV) |
|---|
| Comm. protocol | Modubus RTU |