Autonics KPN5511-030 Bar Graph Temperature Controller KPN5511-030

Model number
KPN5511-030

Autonics KPN5511-030 bar graph temperature controller (KPN Series): 100 - 240 VAC 50/60 Hz supply, IP65 (front panel, IEC standards). Order code note: OUT1,2CUR,SSR*PV+RSV.

Price and availability on request

Request a quote

Sent with the product details: Autonics KPN5511-030 Bar Graph Temperature Controller KPN5511-030.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • High speed sampling of 50 ms and ± 0.3 % display accuracy
  • Enable to check control output operation amount by adopting bar graph
  • Simultaneous heating / cooling control and automatic / manual control for high performance control
  • Selection function of current output or SSR drive output
  • Parameter setting available via PC
  • Communication converter sold separately: SCM-US (USB / Serial converter), SCM-38I (RS232C / RS485 converter), SCM-US48I (USB / RS485 converter)
  • Multi-SV (Max. 4) function (select via digital input terminal)
  • Heater break alarm
  • CT sold separately
  • Multi input / multi range

Specifications

Model
SeriesKPN Series
Order code descriptionOUT1,2CUR,SSR*PV+RSV
Specifications
Power supply100 - 240 VAC 50/60 Hz
Permissible voltage range90 to 110 % of rated voltage
Power consumption≤ 15 VA
Sampling period50 ms
Input specificationRefer to Autonics website
Option input CT input• 0.0-50.0 A (primary current measurement range) • CT ratio: 1/1,000
Option input Remote SV1 - 5 VDC or 4 - 20 mA (Current Input: External resistance 250 Ω)
Option input Digital input• Contact - ON: ≤ 2 kΩ, OFF: ≥ 90 kΩ • Non contact - residual voltage ≤ 1.0 V, leakage current ≤ 0.1 mA
Control output Relay250 VAC 5 A 1a
Control output SSR11 VDC ±2 V, ≤ 20 mA
Control output CurrentDC 4-20 mA or DC 0-20 mA (parameter), load resistance: ≤ 500 Ω
Alarm output Relay250 VAC 3 A 1a
Option output TransmissionDC 4 - 20 mA ( load resistance: ≤ 500 Ω, output accuracy: ±0.3% F.S. ±1-digit)
Option output RS485 Comm.Modbus RTU
Display type7 segment (red, green), control output bar graph (red, green), LED type
Control type Heating, CoolingON/OFF, P, PI, PD, PID Control
Hysteresis• Thermocouple, RTD: 1 to 100 (0.1 to 100.0) ℃/℉ • Analog: 1 to 100 digit
Proportional band (P)0.1 to 999.9 ℃/℉ (0.1 to 999.9%)
Integral time (I)0 to 9,999 sec
Derivative time (D)0 to 9,999 sec
Control cycle (T)• 0.1 to 120.0 sec [relay output model] • 1.0 to 120.0 sec [SSR drive output model]
Manual reset0.0 to 100.0%
Relay life cycle Mechanical≥ 10,000,000 operations
Relay life cycle Electrical≥ 100,000 operations (load resistance: 250 VAC 3 A)
Dielectric strengthBetween the charging part and the case: 3,000 VAC ~ 50/60 Hz for 1 minute
Vibration0.75 mm amplitude at frequency of 5 to 55 Hz in each X, Y, Z direction for 2 hours
Insulation resistance≥ 100 MΩ (500 VDC megger)
Noise immunity±2 kV square shaped noise (pulse width 1 ㎲) by noise simulator R-phase, S-phase
Memory retention≈ 10 years (non-volatile semiconductor memory type)
Ambient temperature-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Protection structureIP65 (front panel, IEC standards)
Insulation typeDouble or reinforced insulation ( dielectric strength between the measuring input part and the power part: 2 kV)
AccessoryBracket
Unit weight (packaged)• KPN52 - : ≈ 160 g (≈ 230 g) • KPN53 - : ≈ 160 g (≈ 230 g) • KPN55 - : ≈ 220 g (≈ 316 g)
Comm. protocolModbus RTU
Accessories
Sold separatelyTerminal protection cover: RHA / RLA-COVER; Communication Converter: SCM-US / SCM-38I / SCM-US48I / SCM-WF48; Current transformer (CT)